Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM05404
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/29/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 08/29/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the ventilation calculations to take into account the different occupancy loads in the project space (a hair salon is not the same as a barber shop). Reference: Sections 403.3 and 403.3.2, IMC 2006. 2. Provide listing information for the clothes dryer to show that the proposed dryer exhaust duct is sized correctly. Reference: Sections 304.1 and 504.6, IMC 2006. |
| 08/29/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/29/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/29/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/29/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/29/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a design for the connection of the mounting shelf for the water heater to the building structure along with structural calculations to show that the water heater is safely supported. Reference: Sections 106.3.1 and 301.2, IPC 2006. |
| 08/30/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/30/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/30/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/14/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |