Permit Number: T12CM05404
Parcel: 123020880

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05404
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/29/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculations to take into account the different occupancy loads in the project space (a hair salon is not the same as a barber shop). Reference: Sections 403.3 and 403.3.2, IMC 2006.
2. Provide listing information for the clothes dryer to show that the proposed dryer exhaust duct is sized correctly. Reference: Sections 304.1 and 504.6, IMC 2006.
08/29/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/29/2012 ROBERT SHERRY WATER REVIEW Approved
08/29/2012 ERIC NEWCOMB ADA REVIEW Passed
08/29/2012 LOREN MAKUS ENGINEERING REVIEW Approved
08/29/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a design for the connection of the mounting shelf for the water heater to the building structure along with structural calculations to show that the water heater is safely supported. Reference: Sections 106.3.1 and 301.2, IPC 2006.
08/30/2012 STEVE SHIELDS ZONING REVIEW Approved
08/30/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
08/30/2012 MARTIN BROWN FIRE REVIEW Approved
09/14/2012 GERRY KOZIOL WWM REVIEW Approved