Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM05367
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/10/2012 | CPIERCE1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
09/11/2012 | GERRY KOZIOL | WWM | REVIEW | Approved | |
09/17/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the size of the dry vent for the combination drain and vent system per Section 916.2, IPC 2006. 2. Revise the waste and vent riser 1/P3 to coordinate with the plumbing new work plan, 1/P1 (the riser diagram has an extra P3A sink). 3. Clarify the note on detail 1/P2 ("check valve????"). |