Permit Number: T12CM05367
Parcel: 13317064C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05367
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2012 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Needs Review
09/11/2012 GERRY KOZIOL WWM REVIEW Approved
09/17/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the size of the dry vent for the combination drain and vent system per Section 916.2, IPC 2006.
2. Revise the waste and vent riser 1/P3 to coordinate with the plumbing new work plan, 1/P1 (the riser diagram has an extra P3A sink).
3. Clarify the note on detail 1/P2 ("check valve????").