Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM05367
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/28/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
08/28/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
08/28/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/28/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/28/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
08/29/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide structural details to show how the water-source heat pump is to be connected to the building structure. Reference: Section 302.1, IMC 2006. 2. Positively pressurized exhaust ducts may not pass through a plenum. Reference: Section 601.4, IMC 2006. |
08/29/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
08/29/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/29/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/29/2012 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/05/2012 | CPIERCE1 | WWM | REVIEW | Needs Review |