Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM05367
Parcel: 13317064C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05367
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2012 STEVE SHIELDS ZONING REVIEW Approved
08/28/2012 PAUL MACHADO ENGINEERING REVIEW Approved
08/28/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/28/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/28/2012 ERIC NEWCOMB ADA REVIEW Passed
08/29/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide structural details to show how the water-source heat pump is to be connected to the building structure. Reference: Section 302.1, IMC 2006.
2. Positively pressurized exhaust ducts may not pass through a plenum. Reference: Section 601.4, IMC 2006.
08/29/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
08/29/2012 ROBERT SHERRY WATER REVIEW Approved
08/29/2012 MARTIN BROWN FIRE REVIEW Approved
08/29/2012 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
09/05/2012 CPIERCE1 WWM REVIEW Needs Review