Review Details: COMMERCIAL - TI
Permit Number - T12CM05280
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/27/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/27/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/27/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Clarify the cold water connection to the clinical sink - it is shown as 1-1/2" in the specifications and 3/4" in the riser diagram. |
| 08/27/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 08/27/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/27/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify the removal of the fire separation for the corridor. What is replacing it? |
| 08/28/2012 | GBONILL1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/28/2012 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |