Review Date Reviewer's Name Type of Review Description Status Comments
09/04/2012 KEN BROUILLETTE FIRE REVIEW Approved
09/07/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. As per the 2006 IBC, Section 406.1.2, the maximum area is 3,000 s.f. So, either provide a fire wall separting the carports into 3,000 s.f. areas or build 3000 s.f. carports areas with a 10' separation as per exception two (5' for each shaded section).
2. The most easterly carport next to the buildings needs to be move approximately 4 parking spaces to the East to meet requiremets odf 2006 IBC, Section 406.1.2, Exception 2.
3. As per table 1106.1, at least 4 shaded spaces are to be accessible.
END OF REVIEW