Permit Number: T12CM05190
Parcel: 140260430

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05190
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2012 TERRY STEVENS ZONING REVIEW Approved
08/22/2012 PAUL MACHADO ENGINEERING REVIEW Approved
08/22/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/22/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S1.1 (GENERAL STRUCTURAL NOTES); STRUCTURAL CALCULATIONS (SHEET 10): THE CALCULATIONS INDICATE WOOD STUD WALL W1 TO BE 2X4 AT 12" O.C., WHILE THE GENERAL STRUCTURAL NOTES (ROUGH CARPENTRY NOTE 8) INDICATES 2X4 AT 16" O.C. CLARIFY.
2. STRUCTURAL CALCULATIONS; SHEET 10: WHERE ARE THE W2 WALL STUDS LOCATED? SHEET 8 OF THE CALCULATIONS HAS NO W2.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/22/2012 ERIC NEWCOMB ADA REVIEW Passed
08/23/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/23/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/23/2012 ROBERT SHERRY WATER REVIEW Approved
08/23/2012 KEN BROUILLETTE FIRE REVIEW Denied Exiting needs to be fixed. Need two exits and overhead doors are not exit doors. Please review exiting section in IFC and IBC
08/24/2012 GERRY KOZIOL WWM REVIEW Passed
08/24/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved