Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/22/2012 | TERRY STEVENS | ZONING | REVIEW | Approved | |
08/22/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
08/22/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/22/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET S1.1 (GENERAL STRUCTURAL NOTES); STRUCTURAL CALCULATIONS (SHEET 10): THE CALCULATIONS INDICATE WOOD STUD WALL W1 TO BE 2X4 AT 12" O.C., WHILE THE GENERAL STRUCTURAL NOTES (ROUGH CARPENTRY NOTE 8) INDICATES 2X4 AT 16" O.C. CLARIFY. 2. STRUCTURAL CALCULATIONS; SHEET 10: WHERE ARE THE W2 WALL STUDS LOCATED? SHEET 8 OF THE CALCULATIONS HAS NO W2. 3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
08/22/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
08/23/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
08/23/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
08/23/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/23/2012 | KEN BROUILLETTE | FIRE | REVIEW | Denied | Exiting needs to be fixed. Need two exits and overhead doors are not exit doors. Please review exiting section in IFC and IBC |
08/24/2012 | GERRY KOZIOL | WWM | REVIEW | Passed | |
08/24/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |