Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T12CM05185
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/27/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | Knox box or key switch required for new barrier gate. |
| 08/29/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Please provide a letter to the building official, Mr. Ron Boose, declaring your steel trusses as a deferred submittal. 2. Please provide a completed certification form for the special inspectors required for this project. 3. The minimum COT lettering size allowed is 3/32" upper and lower case, actual size. Please have your structural engineer to revise his specifications sheet S1.1 to meet this minimum standard and resubmit. SHEET S2.1 AND DETAIL 106 4. The drawings show a casson foundation for the carport structure. While the calculations call for a rectangular foundation 12'x5'x16" deep. Please reconcile. SHEET S3.1 5. Detail 4 framing shows W12x16 whereas the calculations call for 14k joists. Please reconcile 6. Ditto comment 5 for detail 2. There may be additional comments on the structural drawings after the resubmittal. Please rereview the drawings and calculations for continunity prior to resubmittal. END OF REVIEW. |
| 08/31/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 09/10/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Vents for fixtures inside of the buildings shall rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally (polishing building and carwash building). Reference: Section 905.4, IPC 2006. |
| 09/10/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/10/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/11/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/11/2012 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 09/13/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1: INFINITI/CHEVROLET- CAR WASH, POLISHER BUILDING 2: NEED WASTEWATER IWC REVIEW - RUSTY- 724-6200 3: CONNECTING TO EXISTING 2" WATER LINE AND EXISTING ON-SITE PRIVATE SEWER 4: NEED EXISTING WATER METER SIZE AND LOCATION SHOWN ON DRAWINGS AND NEED WATER SUPPLIER VERIFICATION THAT NO UPSIZING IS TO BE DONE |