Permit Number: T12CM05181
Parcel: 105110710

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05181
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2012 KEN BROUILLETTE FIRE REVIEW Approved
08/30/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A101; KEY NOTES: NOTES 1 AND 2 ARE REVERSED ON THE PLAN. REVISE.
2. SHEET A101; KEY NOTES: NOTE 8 WAS NOT ON THE PLAN. VERIFY.
3. SHEET A201; WALL LEGEND: WALLS B, C1, AND D WERE NOT ON THE PLAN. VERIFY.
4. SHEET A201; KEY NOTES: NOTE 18 WAS NOT ON THE PLAN. VERIFY.
5. SHEET A231; KEY NOTES: NOTE 1 WAS NOT ON THE PLAN. VERIFY.
6. SHEET A501; KEY NOTES: NOTE 6 IS INCLUDED ON EVERY INTERIOR ELEVATION ON THIS SHEET. IS THIS 'STOREFRONT WINDOWS' PER THE NOTE? VERIFY.
7. SHEET A502; KEY NOTES: NOTE 6 WAS NOT ON THE ELEVATIONS. VERIFY.
8. SHEET A701; KEY NOTES: NOTE 17 IS INDICATED IN TWO LOCATIONS ON PLAN 03, BUT IS NOT CORRECT. VERIFY.
9. SHEET A701; KEY NOTES: NOTE 18 WAS NOT ON THE PLAN. VERIFY.
10. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/07/2012 ROBERT SHERRY WATER REVIEW Approved
09/07/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/10/2012 ERICA SANCHEZ WWM REVIEW Approved
09/10/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the termination height of the vent for the gas-fired unit heater complies with the requirements of Section 503.6.4 (1), IFGC 2006.
09/13/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved