Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM05178
Parcel: 131132540

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05178
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2012 KEN BROUILLETTE FIRE REVIEW Approved
08/30/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. The line weight is way too light and needs to be beefed up to enable one to read the information on the details:
a. Detail 1/S2.0: Dimensions
b. Vending Roof Framing Plan/S3.0: Roof deck plus beam size call outs
c. Details 1 and 2/S3.0: Beams, bolts, and hangers
d. Details 1, 2, 3 and 4/C4.0: Various items on each detail. Detail 4 is especially bad.
2. Provide title for the vending roof framing plan/S3.0
END OF REVIEW
09/06/2012 ROBERT SHERRY WATER REVIEW Denied 1. Clarify the size of the water meter; the plumbing plan shows an existing 1-1/2" meter but the calculations are based on the installation of a new 1" meter.
2. Is a new reduced pressure backflow preventer to be installed, as shown by the detail or will the existing reduced pressure backflow preventer be retained.
09/06/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the water demand calculations. The calculations show both 22 GPM and 27.5 GPM for the car wash equipment. Water demand for appliances and equipment shall be added to the demand determined for the plumbing fixtures. Reference: Section A2.2, UPC 2006.
09/06/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/06/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/07/2012 GERRY KOZIOL WWM REVIEW Approved