Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM05178
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 08/30/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. The line weight is way too light and needs to be beefed up to enable one to read the information on the details: a. Detail 1/S2.0: Dimensions b. Vending Roof Framing Plan/S3.0: Roof deck plus beam size call outs c. Details 1 and 2/S3.0: Beams, bolts, and hangers d. Details 1, 2, 3 and 4/C4.0: Various items on each detail. Detail 4 is especially bad. 2. Provide title for the vending roof framing plan/S3.0 END OF REVIEW |
| 09/06/2012 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Clarify the size of the water meter; the plumbing plan shows an existing 1-1/2" meter but the calculations are based on the installation of a new 1" meter. 2. Is a new reduced pressure backflow preventer to be installed, as shown by the detail or will the existing reduced pressure backflow preventer be retained. |
| 09/06/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Clarify the water demand calculations. The calculations show both 22 GPM and 27.5 GPM for the car wash equipment. Water demand for appliances and equipment shall be added to the demand determined for the plumbing fixtures. Reference: Section A2.2, UPC 2006. |
| 09/06/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/06/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 09/07/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |