Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/27/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A2.1.1A; FLOOR PLAN 2: A NOTE 7 IS INDICATED AT A DOOR ON THE NORTH WALL OF THE ELEVATOR #1 MACHINE ROOM. IS THIS CORRECT? 2. SHEET A3.0.1; KEYNOTES: KEYNOTE 6 WAS NOT FOUND IN THE SECTIONS. VERIFY. 3. SHEETS A3.0.1, A3.0.2, AND A3.1.1; GENERAL MASONRY NOTES: INCLUDE IN THE NOTE THE MASONRY INFILL SPACING OF SOLID GROUTED CELLS AND THE REINFORCING SIZE IN THOSE CELLS. PROVIDE A DETAIL INDICATING THE DOWEL/EPOXY INTO THE EXISTING WALL AS REQUIRED. 4. GENERAL: SPECIAL INSPECTIONS WILL BE REQUIRED FOR STRUCTURAL MASONRY INFILL AND EPOXY ANCHORS. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
09/04/2012 | GERRY KOZIOL | WWM | REVIEW | Passed | |
09/04/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
09/04/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/04/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/04/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
09/05/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved |