Permit Number: T12CM05171
Parcel: 117200270

Address:
260 S CHURCH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05171
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A2.1.1A; FLOOR PLAN 2: A NOTE 7 IS INDICATED AT A DOOR ON THE NORTH WALL OF THE ELEVATOR #1 MACHINE ROOM. IS THIS CORRECT?
2. SHEET A3.0.1; KEYNOTES: KEYNOTE 6 WAS NOT FOUND IN THE SECTIONS. VERIFY.
3. SHEETS A3.0.1, A3.0.2, AND A3.1.1; GENERAL MASONRY NOTES: INCLUDE IN THE NOTE THE MASONRY INFILL SPACING OF SOLID GROUTED CELLS AND THE REINFORCING SIZE IN THOSE CELLS. PROVIDE A DETAIL INDICATING THE DOWEL/EPOXY INTO THE EXISTING WALL AS REQUIRED.
4. GENERAL: SPECIAL INSPECTIONS WILL BE REQUIRED FOR STRUCTURAL MASONRY INFILL AND EPOXY ANCHORS.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/04/2012 GERRY KOZIOL WWM REVIEW Passed
09/04/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/04/2012 ROBERT SHERRY WATER REVIEW Approved
09/04/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/04/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/05/2012 KEN BROUILLETTE FIRE REVIEW Approved