Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T12CM05162
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/05/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | See Tank Permit T12BU01039 |
| 09/12/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM05162 All request per 2005 NEC 1. Outline (shade) Classified Areas, Class 1 Div 1, and Class 1 Div 2. 2. Show location of seals required per 514.9. 3. Show location of EPO Switch per 514.11 4. Indicate on Sheet E-1 "Wiring and Equipment above Class 1 Locations" to comply with 514.7. 5. Indicate on Sheet E-1, undergroung wiring to comply with 514.8. 6.Indicate on Sheet E-1, "Provisions for Maintenance and Service of Dispensing Equipment" to comply with 514.13. 7. Plan indicates Control Panel-Contractor to Provide Main Power, provide on this plan how the power is to be provided and show location and provide calculation source can provide power. Ray T Majuta Elect Pln Review PDSD, C of Tuc 9/12/2012 520/837/4988 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/17/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |