Permit Number: T12CM05161
Parcel: 11005014C

Review Status: Completed

Review Details: OTHER

Permit Number - T12CM05161
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM05161
1. TEP SR-510, AIC at utility transformer is 75,100 aic, the MSB gear shows rating of 65KAIC, provid a fault current Calculation From Utility through to 10KAIC level.

RT Majuta
DSD, City of Tuc,
8/21/2012

Final Status

Task End Date Reviewer's Name Type of Review Description