Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T12CM05161
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/21/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM05161 1. TEP SR-510, AIC at utility transformer is 75,100 aic, the MSB gear shows rating of 65KAIC, provid a fault current Calculation From Utility through to 10KAIC level. RT Majuta DSD, City of Tuc, 8/21/2012 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/22/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |