Permit Number: T12CM05158
Parcel: 125100080

Address:
3811 E 2ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM05158
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2012 KEN BROUILLETTE FIRE REVIEW Approved
11/05/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/09/2012 GERRY KOZIOL WWM REVIEW Denied 1: ANGEL CHARITY REUNION HOUSE - DP12-0137
2: 1" WATER METER - NEED WATER SUPPLIER INFORMATION FOR CREDIT
3: NEED CAPACITY EVALUATION -KURT STEMM 740-6607
NEED DP REVIEW, NEED MANHOLE CONSTRUCTION PERMIT
11/09/2012 STEVE SHIELDS ZONING REVIEW Approved
11/20/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not addressed by the architect. [Original comment: Provide a detail to show that the construction of the shower receptors comply with the requirements of Section 417.5.2, IPC 2006.]
11/20/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The energy code compliance calculations were not included in this submittal. The architectural drawings and the specifications do not show the U-factors and SHGF-values for the skylights and the tempered glass. [Original comment: Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.]
2. Comment not resolved; a 10"-diameter duct with a flow rate of 800 CFM has a mean velocity of 1466 FPM. [Original comment: Revise the size of the grease duct for the Type I hood to provide a minimum velocity of 1500 feet per minute. Reference: Section 506.3.4, IMC 2006, as amended by the City of Tucson.]
3. The architectural interior elevations show plywood cabinets touching the sides of the hood and the wall behind the hood is constructed with wood studs and has only a stainless steel backsplash. The shop drawings for the hood do not indicate zero-clearance construction. [Original comment: Show that the hood installation complies with Section 507.9, IMC 2006 for clearances (e.g. 18" clearance to combustibles such as cabinets, and with a smooth, cleanable, non-absorbent, and non-combustible material installed between the hood and the wall, and extending 18" beyond the hood).]
4. Comment not resolved; show that the units supplying make up air for the kitchen hood are electrically interlocked to the exhaust fan. [Original comment: Provide adequate make up air for the kitchen exhaust hood. Show that the unit supplying make up air for the kitchen hood is electrically interlocked to the exhaust fan. Reference: Section 508.1, IMC 2006.]