Permit Number: T12CM05158
Parcel: 125100080

Address:
3811 E 2ND ST

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T12CM05158
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET G1.0; CODE ANALYSIS: AT THE OCCUPANT LOAD CALCULATION, INDICATE THE ALLOWABLE NUMBER OF OCCUPANTS IN THE 4570 SF AREA (NONE SHOWN).
2. SHEET G1.0; CODE ANALYSIS: FIRE RESISTANCE REQUIREMENTS FOR INTERIOR WALLS ARE SPECIFIED IN THE IBC SECTION 708. ADD THAT REFERENCE TO THE DRAWINGS. IT APPEARS THE WALLS BETWEEN SLEEPING UNITS COULD REQUIRE ONLY A 1/2 HOUR FIRE RESISTANCE RATING PER THE IBC SECTION 708.3 (EXCEPTION 2). VERIFY.
3. SHEET S1.2; DEFERRED SUBMITTALS: ALL DEFERRED SUBMITTALS MUST BE APPROVED IN WRITING BY RON BOOSE (BUILDING OFFICIAL) BEFORE THOSE SUBMITTALS WILL BE REVIEWED. RON.BOOSE@TUCSONAZ.GOV.
4. SHEET S1.5; DETAILS T44 AND T45: ARE THESE DETAILS PERTINENT TO THIS PROJECT? IF SO, PROVIDE STRUCTURAL CALCULATIONS.
5. SHEET S2.1; FOUNDATION PLAN; THE PLAN DOES NOT SHOW OR CALL-OUT ALL C2 COLUMNS. REVISE.
6. SHEET S2.1 (FOUNDATION PLAN); STRUCTURAL CALCULATIONS (SHEET 69): THE CALCULATIONS INDICATE SW4 SHOULD HAVE 8d NAILS AT 4" OC, WHILE THE PLAN INDICATES SW1 (8d NAILS AT 6" OC). CLARIFY.
7. SHEET S3.1 (LOW ROOF FRAMING PLAN); STRUCTURAL CALCULATIONS: THE COLUMN C3 DENOTED ON THE PLAN HAS NO CALCULATION. PROVIDE.
8. SHEET S3.1; LOW ROOF FRAMING PLAN: THE PLAN DOES NOT CALL-OUT ALL C2 AND C3 COLUMNS. REVISE.
9. SHEET S4.1; DETAILS 102 AND 104: INDICATE THE STEM WALL WIDTHS AND REINFORCING.
10. SHEET S5.2; DETAIL 228: INDICATE ON THIS DETAIL THE STEEL BEAM AND METAL ROOF DECK (PER THE DETAIL TITLE) IN RELATION TO THE WOOD FRAMING.
11. SHEET S5.2; DETAIL 231: THE DETAIL INDICATES THE WOOD STUD WALL EXTENDS PAST THE WOOD BEAM ON BOTH SIDES. THE STUD WALL EXTENDS TO THE HIGH ROOF ON ONE SIDE ONLY. VERIFY.
12. STRUCTURAL CALCULATIONS; SHEET 72: SHEARWALL 7 IS NOT LOCATED ON THE CALCULATION KEY PLAN (SHEET 62). PROVIDE.
13. STRUCTURAL CALCULATIONS: DID NOT FIND THE LEDGER DESIGNS. PROVIDE.
14. SHEET A0.1; SITE PLAN 1: PROVIDE A DIMENSION FROM THE PROPERTY LINE TO THE BUILDING (ON THREE SIDES) TO EXHIBIT IBC TABLE 602 REQUIREMENTS ARE MET.
15. SHEET A0.3; DETAIL 11: PROVIDE A NOTE ON THE CMU SCREEN WALL TO REFERENCE STRUCTURAL FOR WALL REINFORCING.
16. SHEET A1.1; FLOOR PLAN: PROVIDE A NORTH ARROW ON THE PLAN.
17. SHEET A1.1; FLOOR PLAN: THE DOORS FROM THE MECHANICAL ROOM AND THE JANITOR'S ROOM REDUCE THE EGRESS IN THE HALL AND THEREFORE DO NOT MEET THE REQUIREMENTS OF THE IBC SECTION 1005.2. REVISE.
18. SHEET A1.1; KEYNOTES: KEYNOTE REFERENCE 15.13 HAS BEEN REMOVED DUE TO A GENERAL NOTE. REVISE.
19. SHEET A1.1 (FLOOR PLAN); SHEET A5.2 (DETAILS 1 AND 3): ON THE PLAN, THE WALLS (TYPE 3) ON THE NORTH AND WEST SIDES OF THE OPEN OFFICE INDICATE 42" HIGH, WHILE THE DETAILS SHOW 36" HIGH. CLARIFY.
20. SHEET A1.1 (FLOOR PLAN); SHEET A2.1 (WALL TYPES): THE FLOOR PLAN AND SHEET A2.1 INDICATE SIX WALL TYPES, BUT 'WALL TYPES' LISTED AT THE BOTTOM OF SHEET A1.1 LISTS ONLY THREE. CLARIFY.
21. SHEET A1.1; BATHROOM PLAN 3: INDICATE ON THE PLAN ALL GRAB BARS, SEATS, SHOWER HEADS, ETC.
22. SHEET A1.1; FLOOR PLAN: PER THE IBC SECTION 1107.5.1.1, AT LEAST ONE UNIT SHALL BE ACCESSIBLE. INDICATE ON THE PLAN THE ACCESSIBLE UNIT.
23. SHEET A1.1; FLOOR PLAN: PER THE IBC SECTION 1107.5.1.2, THE REMAINING SLEEPING UNITS MUST MEET TYPE B UNITS. INDICATE ON THE PLAN A NOTE FOR THIS REQUIREMENT.
24. SHEET A1.1; FLOOR PLAN: THE BATHROOM IN THE SOUTHEAST CORNER OF THE BUILDING WILL REQUIRE ACCESSIBILITY. IT WILL BE A PUBLIC TOILET AND MUST MEET ACCESSIBILITY REQUIREMENTS. VERIFY.
25. SHEET A1.1; FLOOR PLAN: INDICATE THE DRINKING FOUNTAIN ON THE PLAN.
26. SHEET A1.1; FLOOR PLAN: THE KITCHEN IS REQUIRED TO BE ACCESSIBLE PER THE IBC SECTION 1109.4. REVISE THE COUNTER HEIGHTS AS REQUIRED. VERIFY.
27. SHEET A1.2; DOOR SCHEDULE: VERIFY THE DOORS INDICATED PROVIDE ADEQUATE CLEARANCE AT THE ACCESSIBLE AREAS.
28. SHEET A5.1; ELEVATION 6: GRAB BARS ARE INDICATED IN THE NON-ACCESSIBLE RESTROOM. IS THAT THE INTENT?
29. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/29/2012 MARTIN BROWN FIRE REVIEW Denied 1) Exits do not appear to conform to 2006 IBC, section 1015.2.1, exception 2 (1/3 diagonal dimension of area served. Please provide revised exiting plan or prove code conformance.
2) Tucson Fire would prefer NO double check valve on fire service. Verify Tucson Water requirements and remove if possible. Check valve on riser would be required. Remote Fire Department Connection is required.
3) Note on cover sheet says standpipes are provided. No standpipes on job. Please correct Sheet G1.0.
4) Verify hardware on doors conforms to chapter 10 of the IBC.
09/07/2012 GERRY KOZIOL WWM REVIEW Denied 1: ANGEL CHARITY REUNION HOUSE -DP12-0138
2: 1" WATER METER- NEED WATER SUPPLIER INFORMATION FOR CREDIT
3: NEED CAPACITY EVALUATION- KURT STEMM 740-6607
4: NEED 3RD FLOOR REVIEW OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER - CHAD AMATEAU - 740-6547
09/10/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a detail to show that the construction of the shower receptors comply with the requirements of Section 417.5.2, IPC 2006.
2. Clarify the water supply to the drinking fountain, P8; as shown on sheet P1.1, it appears to have only a hot water supply. Reference: Section 106.3.1, IPC 2006.
09/10/2012 ROBERT SHERRY WATER REVIEW Approved
09/11/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/11/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Revise the size of the grease duct for the Type I hood to provide a minimum velocity of 1500 feet per minute. Reference: Section 506.3.4, IMC 2006, as amended by the City of Tucson.
3. If the proposed Type I hood is not a factory-built hood, listed and labeled as complying with UL 710, provide construction details for the hood and revise the air flow of the hood to comply with the requirements of Section 507.13.3, IMC 2006. Reference: Section 507.1, IMC 2006.
4. Provide information to show that the operation of the Type I hood and the hood exhaust fan complies with Section 507.2.1.1, IMC 2006.
5. Provide the installed weight of the Type I hood along with structural calculations and details to show that the Type I hood and its associated exhaust fan is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.
6. Show that the hood installation complies with Section 507.9, IMC 2006 for clearances (e.g. 18" clearance to combustibles such as cabinets, and with a smooth, cleanable, non-absorbent, and non-combustible material installed between the hood and the wall, and extending 18" beyond the hood).
7. Provide adequate make up air for the kitchen exhaust hood. Show that the unit supplying make up air for the kitchen hood is electrically interlocked to the exhaust fan. Reference: Section 508.1, IMC 2006.
09/12/2012 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Reunion House
T12CM05158
Building Plan (1st Review)

TRANSMITTAL DATE: September 12, 2012

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the building plan until a development package has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
09/18/2012 PAUL MACHADO ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/24/2012 CPIERCE1 REJECT SHELF Completed