Permit Number: T12CM05046
Parcel: 11310109B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM05046
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/21/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/21/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The flow control devices are not shown as being installed per the manufacturer's instructions (e.g. venting, accessibility). Install the flow control device correctly or install a hydromechanical grease intercepter with an integral flow control device. [Third comment: Flow control devices shall be installed per the manufacturer's instructions.] [Second comment: The specified hydromechanical grease interceptor (Zurn GT-2700-50) does not have an integral flow control device. See the Zurn engineering bulletin for an explanation: http://content.zurn.com/web_documents/pdfs/miscellaneous/SD10.pdf ][Original comment: Detail 9/P-3 shows the installation of a flow control device for the 3-compartment sink but nothing indicates the installation of flow control devices for the other three fixtures that are connected to the hydromechanical grease interceptor. Show how the total flow to the hydromechanical grease interceptor is to be controlled or provide a hydromechanical grease interceptor with an integral flow control device. Reference: Sections 1003.2 and 1003.3.4.2, IPC 2006.]
12/24/2012 SPOWELL1 WWM REVIEW Needs Review