12/19/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
12/19/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Flow control devices shall be installed per the manufacturer's instructions. [Second comment: The specified hydromechanical grease interceptor (Zurn GT-2700-50) does not have an integral flow control device. See the Zurn engineering bulletin for an explanation: http://content.zurn.com/web_documents/pdfs/miscellaneous/SD10.pdf ][Original comment: Detail 9/P-3 shows the installation of a flow control device for the 3-compartment sink but nothing indicates the installation of flow control devices for the other three fixtures that are connected to the hydromechanical grease interceptor. Show how the total flow to the hydromechanical grease interceptor is to be controlled or provide a hydromechanical grease interceptor with an integral flow control device. Reference: Sections 1003.2 and 1003.3.4.2, IPC 2006.]
12/19/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the pipe sizes for the condensate drain system. The minimum size for a condensate drain is ¾"; the minimum size for a condensate drain serving two A/C units is 1". Reference: Section 307.2.2, IMC 2006, as amended by the City of Tucson.
[Second comment: Show the size of the common condensate drain.] [Original comment: Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson.]
12/20/2012 CPIERCE1 WWM REVIEW Needs Review