Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM05046
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/19/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/19/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Flow control devices shall be installed per the manufacturer's instructions. [Second comment: The specified hydromechanical grease interceptor (Zurn GT-2700-50) does not have an integral flow control device. See the Zurn engineering bulletin for an explanation: http://content.zurn.com/web_documents/pdfs/miscellaneous/SD10.pdf ][Original comment: Detail 9/P-3 shows the installation of a flow control device for the 3-compartment sink but nothing indicates the installation of flow control devices for the other three fixtures that are connected to the hydromechanical grease interceptor. Show how the total flow to the hydromechanical grease interceptor is to be controlled or provide a hydromechanical grease interceptor with an integral flow control device. Reference: Sections 1003.2 and 1003.3.4.2, IPC 2006.] |
| 12/19/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the pipe sizes for the condensate drain system. The minimum size for a condensate drain is ¾"; the minimum size for a condensate drain serving two A/C units is 1". Reference: Section 307.2.2, IMC 2006, as amended by the City of Tucson. [Second comment: Show the size of the common condensate drain.] [Original comment: Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson.] |
| 12/20/2012 | CPIERCE1 | WWM | REVIEW | Needs Review |