Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM05046
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/15/2012 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Dunkin Donuts - 2553 N. Campbell Avenue T12CM05046 Building Plan (2nd Review) TRANSMITTAL DATE: November 15, 2012 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning can not approve the building plan until a development package has been approved. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 11/19/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/19/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show the size of the common condensate drain. [Original comment: Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson.] |
| 11/19/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The specified hydromechanical grease interceptor (Zurn GT-2700-50) does not have an integral flow control device. See the Zurn engineering bulletin for an explanation: http://content.zurn.com/web_documents/pdfs/miscellaneous/SD10.pdf [Original comment: Detail 9/P-3 shows the installation of a flow control device for the 3-compartment sink but nothing indicates the installation of flow control devices for the other three fixtures that are connected to the hydromechanical grease interceptor. Show how the total flow to the hydromechanical grease interceptor is to be controlled or provide a hydromechanical grease interceptor with an integral flow control device. Reference: Sections 1003.2 and 1003.3.4.2, IPC 2006.] 2. Show the size of the roof drain and drain leader noted on sheet A-2.1 (Keynote #3) and shown in detail 1/A-10. |
| 11/27/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1: DUNKIN DONUTS 2: CONNECTION TO EXISTING ON SITE PRIVATE SEWER PER DRAWINGS AND PERMIT #ZP-8499 DATED 05/30/73 3: CONNECTING TO EXSITING 1" WATER METER PER DRAWINGS- NEED WATER SUPPLIER VERIFICATION OF OF EXISTING WATER METER 4: NEED WASTEWATER/IWC/REVIEW OF 50GPM/100# INTERIOR GREASE TRAP- RUSTY 724-6200 - 2024 W EL CAMINO DEL CERRO |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/18/2012 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 12/18/2012 | CPIERCE1 | REJECT SHELF | Completed |