Permit Number: T12CM05044
Parcel: 10602264A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05044
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2012 KEN BROUILLETTE FIRE REVIEW Approved
08/27/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET 1.2; H/C TOILET ELEVATION E: PROVIDE A VERTICAL GRAB BAR PER THE ICC/ANSI A117.1-2003 FIGURE 604.5.1.
2. SHEET 1.2; H/C TOILER ELEVATION E: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE DIMENSIONS.
3. SHEET 1.2; FLOOR PLAN: THE PLAN INDICATES A NEW WALL-SUPPORTED WATER HEATER (MINIMUM 40 GALLON PER PLUMBING SHEET 15.1). PROVIDE STRUCTURAL CALCULATIONS FOR A SUPPORT RACK, FOR THE CONNECTION OF THE RACK TO THE WALL STUDS, AND THE DESIGN OF THE WALL STUDS. PROVIDE DETAILS ON THE FULL-SIZE DRAWINGS INDICATING THESE DESIGN ISSUES.
4. SHEET 1.2; FLOOR PLAN: PROVIDE AN ELEVATION/DETAIL INDICATING THE NEW COUNTERTOP/SINK AREA IN THE BREAK ROOM MEETS ACCESSIBILITY REQUIREMENTS.
5. GENERAL: PROVIDE STRUCTURAL CALCULATIONS TO INDICATE THE CAPABILITY OF THE EXISTING ROOF STRUCTURE TO SUPPORT THE NEW ROOFTOP UNIT. PROVIDE DETAILS ON THE FULL-SIZE DRAWINGS INDICATING NEW FRAMING REQUIRED AT THE NEW ROOFTOP UNIT.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/29/2012 CPIERCE1 WWM REVIEW Needs Review
08/29/2012 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review
08/29/2012 CPIERCE1 WATER REVIEW Needs Review
08/29/2012 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/29/2012 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Needs Review