Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - COMM
Permit Number - T12CM04995
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/13/2012 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 08/13/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/13/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Maximum travel distance is 100' as per table 1019.2. Actual distance is 130'. Need a second exit. 2. Please provide door and hardware schedule. 3. Door to office 107 does not comply with ICC A1171., Section 404.2.3.1. 4. Show 1st floor plan with toilets and tentant layout. a. Show all of existing basement floor plan layout. b. Show location of water dispensers and service sink. END OF REVIEW |
| 08/14/2012 | KEN BROUILLETTE | FIRE | REVIEW | Denied | 1. Maximum travel distance is 100' as per table 1019.2. Need a second exit. 2. Please provide door and hardware schedule. |
| 09/14/2012 | CPIERCE1 | ADA | REVIEW | Needs Review | |
| 09/14/2012 | CPIERCE1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |