Permit Number: T12CM04934
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM04934
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2012 TERRY STEVENS ZONING REVIEW Approved
08/10/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
08/10/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/10/2012 ROBERT SHERRY WATER REVIEW Approved
08/10/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/10/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
08/10/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved Provide the material standards for the water distribution piping materials and for the drainage piping and fittings. Reference: Sections 605.3 and 702, IPC 2006.
08/10/2012 ERIC NEWCOMB ADA REVIEW Passed
08/13/2012 KEN BROUILLETTE FIRE REVIEW Approved
08/14/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM04934
4500 N Oracle RD #470

1. Provide 2006 IECC Budget Lighing Report, COMCHECK will be ok.
2. Mechanical Plans Exmanier has requested compliance with interlocking supplied air to restrooms and exhausted air, will need to verify how it is to be done electrically.
Ray Majuta
Elect PLn Ck
DPD City of Tucson
8/14/2012
Ray.Majuta@tucsonaz.gov
08/20/2012 GERRY KOZIOL WWM REVIEW Approved