Permit Number: T12CM04917
Parcel: 123130960

Address:
2125 N EUCLID AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM04917
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 8-24-12
Activity: T12CM04917
Address: 2125 N. Euclid
Applicant: David Espinose

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

FLOOR PLAN:
1. Show the location of attic access min. 22"x30", R807.
2. Provide a floor or landing outside exterior doors, R311.4.3.

FOUNDATION PLAN:
3. Provide a note for termite treatment, R320 as amended.

SECTIONS - DETAILS:
4. Provide an attic space ventilation calculation for the existing roof area if the new addition impacts the existing eave vents, R806.2.
5. Provide a minimum opening of 22" by 30" for access and ventilation between over-framed assemblies (>30 S.F.), R807.

MECHANICAL PLAN:
6. Specify combustion air openings in accordance with chapter 17 of the International Residential Code.

ELECTRICAL PLAN:
7. Provide wall or floor receptacles within six feet of the doorway to addition, E3801.2.
8. Bedroom outlets shall be protected with combination-type arc-fault breakers (including lights and smoke detectors), E3802.12.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2012 GERARDO BONILLA APPROVAL SHELF Completed
10/01/2012 GERARDO BONILLA OUT TO CUSTOMER Completed
10/01/2012 GERARDO BONILLA REJECT SHELF Completed