Permit Number: T12CM04912
Parcel: 11016221A

Address:
6255 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM04912
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2012 KEN BROUILLETTE FIRE REVIEW Approved
08/21/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/27/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/27/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the floor of the restroom so it slopes toward the floor drain. Reference: Section 411.2, UPC 2006.
08/27/2012 ROBERT SHERRY WATER REVIEW Approved
09/04/2012 GERRY KOZIOL WWM REVIEW Approved
09/06/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM04912
6255 E Grant Rd
Costco Tire Center

1. Provide panel schedule for Panel TS1 and show loads.
2. How will new AC-36 affect Panel load ?

Ray T Majuta
Elect Pln Ck
DSD,C of Tuc
9/7/2012
Ray.Majuta@tucsonaz.gov
09/07/2012 STEVE SHIELDS ZONING REVIEW Approved