Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM04912
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/14/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 08/21/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/27/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/27/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the floor of the restroom so it slopes toward the floor drain. Reference: Section 411.2, UPC 2006. |
| 08/27/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/04/2012 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/06/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM04912 6255 E Grant Rd Costco Tire Center 1. Provide panel schedule for Panel TS1 and show loads. 2. How will new AC-36 affect Panel load ? Ray T Majuta Elect Pln Ck DSD,C of Tuc 9/7/2012 Ray.Majuta@tucsonaz.gov |
| 09/07/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved |