Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM04896
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/13/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 08/23/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Please provide calculations for all structural modifications. 2. Please provide structural calculations for the new roof top mounted condensing unit. 3. Please send a letter listing the steel stairs as a deferred submittal to the building official, Mr. Ron Boose. 4. Please provide a completed certification form for the listed special inspectors required for this project. END OF REVIEW |
| 09/05/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM04896 4400 E Broadway Bl TI Elevators 1. Distribution Panel A-9 (200 amps) is showing the following: 2 -100 A Elevators 1 and 2 2 - 30 A Cooling Towers 1 - 30 A Exhaust Fan 1- 60 A Relief Fan 1 - 50 A 30KVA Trans, These are shown as overcurrent devices on Panel A-9, even tho note on Sheet E1.1 indicates New Elevator Motors to match removed, please provide a load calculation for A-9. 2. 2005 NEC - 620.62 requires Selective Coordination of overcurrent devices for elevators, since all electrical is new, these need to be provided. Ray T Majuta Elect Pln Review DSD, C of Tuc 9/5/2012 Ray.Majuta@tucsonaz.gov |