Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM04866
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/08/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/08/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/08/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/08/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/08/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A3; ROOF-TOP FRAMING AT NEW A/C UNIT: THE NEW UNIT WEIGHT IS 800 POUNDS ON THE EXISTING ROOF STRUCTURE. PROVIDE STRUCTURAL CALCULATIONS INDICATING THE EXISTING STRUCTURE IS CAPABLE OF SUPPORTING THE NEW LOAD. 2. SHEET A3; TOILET ACCESSORIES: PROVIDE THE LOCATION OF THE PAPER DISPENSER PER THE ICC/ANSI A117.1-2003, FIGURE 604.7. 3. SHEET A3; TOILET ACCESSORIES: PROVIDE THE LOCATION OF THE VERTICAL GRAB BAR FROM THE BACK WALL PER THE ICC/ANSI A117.1-2003, FIGURE 604.5.1. |
| 08/08/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/08/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/08/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 08/08/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/09/2012 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 08/10/2012 | MARTIN BROWN | FIRE | REVIEW | Approved |