Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM04844
Parcel: 11006014P

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM04844
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2013 MARTIN BROWN FIRE REVIEW Approved
09/04/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S1; GENERAL STRUCTURAL NOTES: NOTE 1 INDICATES THE 2006 IBC. REVISE THAT NOTE TO THE 2012 EDITION, AND VERIFY CALCULATIONS AND DRAWINGS MEET THAT CRITERIA, ALONG WITH THE AMENDMENT OF SECTION 1609.5.1 CONCERNING MICROBURST RESISTANCE.
2. SHEET S1; GENERAL STRUCTURAL NOTES: NOTE 11 INDICATES THE 2006 IBC. REVISE THAT NOTE TO THE 2012 EDITION, AND VERIFY CALCULATIONS AND DRAWINGS MEET THAT CRITERIA, ALONG WITH THE AMENDMENT OF SECTION 1609.5.1 CONCERNING MICROBURST RESISTANCE.
3. SHEET S1; DETAIL 06: NOTE 02 INDICATES TO "REFER TO GSN FOR FASTENING". NO NOTE WAS LOCATED FOR THIS FASTENING. INDICATE IN THE CALCULATIONS THE CONNECTION TYPE AND PATTERN, AND SHOW THIS ON THE DRAWINGS.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/06/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
09/06/2013 CPIERCE1 REJECT SHELF Completed