Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T12CM04844
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/15/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/04/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET S1; GENERAL STRUCTURAL NOTES: NOTE 1 INDICATES THE 2006 IBC. REVISE THAT NOTE TO THE 2012 EDITION, AND VERIFY CALCULATIONS AND DRAWINGS MEET THAT CRITERIA, ALONG WITH THE AMENDMENT OF SECTION 1609.5.1 CONCERNING MICROBURST RESISTANCE. 2. SHEET S1; GENERAL STRUCTURAL NOTES: NOTE 11 INDICATES THE 2006 IBC. REVISE THAT NOTE TO THE 2012 EDITION, AND VERIFY CALCULATIONS AND DRAWINGS MEET THAT CRITERIA, ALONG WITH THE AMENDMENT OF SECTION 1609.5.1 CONCERNING MICROBURST RESISTANCE. 3. SHEET S1; DETAIL 06: NOTE 02 INDICATES TO "REFER TO GSN FOR FASTENING". NO NOTE WAS LOCATED FOR THIS FASTENING. INDICATE IN THE CALCULATIONS THE CONNECTION TYPE AND PATTERN, AND SHOW THIS ON THE DRAWINGS. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/06/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |
| 09/06/2013 | CPIERCE1 | REJECT SHELF | Completed |