Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM04819
Parcel: 13101053B

Address:
1255 S SWAN RD

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T12CM04819
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. With the addition of building 2, 10 occupants are added to the total occupancy load which has not been indicated on the drawings.
a. It appears that the existing building 1, plus office, plus service bay will have an approximate occupancy load of around 14. Please confirm and add calculations to the drawings.
b. Add 10 more occupants to the already +/- 14 which equals a total of +/- 24 occupants.
c. As per the 2006 IBC, section 2002.2 exception 2, separate toilet rooms are now required for men and women. Please provide another toilet room which must be accessible.
2. Water dispenser and service sink are not shown. Please provide a complete floor plan of the existing facilities showing all toilets, water dispensers and service sink.
3. With a building 80' long, how can you have a travel distance of 75'? Please provide another exit as required by tables 1019.1 and 1019.2.
4. Please provide a detail of the cooler mounting brackets showing attachment to structural memebers of the metal building and support elements as required by the structutral calculations. Insure all elements of the cooler support have been analyized by the structural engineer including the structural members of the metal building.
END OF REVIEW
10/22/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/22/2012 TERRY STEVENS ZONING REVIEW Denied Zoning cannot approve the building plan until the site plan has been approved.