Permit Number: T12CM04819
Parcel: 13101053B

Address:
1255 S SWAN RD

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T12CM04819
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2012 KEN BROUILLETTE FIRE REVIEW Approved
08/13/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Need approved site plan.
2. Need foundation structural calculations.
3. Need toilets as per Section 2902
4. Need Water dispensers
5. Need service sink.
6. With 30 occupants, two exits are required as per table 1019.2.
a. Please show on drawings the actual occupant load calculation and maximum number of occupants allowed by the 2006 IBC.
7. Need Structural calculations for wall mounted Evaporative coolers.
END OF REVIEW
08/13/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
08/22/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide plumbing plans for the new work required by the building review, including water isometrics and waste and vent isometrics. Reference: Section 103.2.3, UPC 2006.
08/22/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a mechanical design for the proposed building addition that clearly shows that the installation will comply with the requirements of Sections 302, 306, 309, and 920, as well as Chapter 13, IMC 2006. Reference: Section 106.3.1, IMC 2006.
2. Provide specifications and listing information for the mechanical equipment. Reference: Section 301, IMC 2006.
3. Demonstrate energy code compliance for the building envelope using calculations based on the current code. Reference: Section 101.4, International Energy Conservation Code 2006.
08/22/2012 ROBERT SHERRY WATER REVIEW Denied Provide a site plan showing water service to the building along with the location and size of the water meter and the size, location, and type of backflow preventer.
08/27/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM04819
1255 S Swan
Automotive Repair

1. Must be determined and must show on Electrical if the type of repair is considered Major or Minor Repair Garage as described in the 2005 NEC,Section 511.3.A, this will determine if the repair area is unclassified or or classified. Each has different wiring methods. Review the 2005 NEC Handbook, 511.3 to determine .
2. Provide a fixture schedule showing the type of fixture, lamp and wattage used . This is required for TI's.
3. The 2005 NEC, Section 511.12 requires GFCI protection for receptacles in repair garages.Show on plan.
4. Identfy circuits B-23 and 25 on plan.

Ray T Majuta
Electrical Plan Review
PDSD, City of Tucson
8/27/2012
Ray.Majuta@tucsonaz.gov
08/29/2012 TERRY STEVENS ZONING REVIEW Denied Zoning cannot approve the building plan until the site plan has been approved.
08/29/2012 GERRY KOZIOL WWM REVIEW Passed
09/04/2012 PAUL MACHADO ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/13/2012 CINDY AGUILAR OUT TO CUSTOMER Completed