| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/13/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 08/13/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Need approved site plan. 2. Need foundation structural calculations. 3. Need toilets as per Section 2902 4. Need Water dispensers 5. Need service sink. 6. With 30 occupants, two exits are required as per table 1019.2. a. Please show on drawings the actual occupant load calculation and maximum number of occupants allowed by the 2006 IBC. 7. Need Structural calculations for wall mounted Evaporative coolers. END OF REVIEW |
| 08/13/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 08/22/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide plumbing plans for the new work required by the building review, including water isometrics and waste and vent isometrics. Reference: Section 103.2.3, UPC 2006. |
| 08/22/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a mechanical design for the proposed building addition that clearly shows that the installation will comply with the requirements of Sections 302, 306, 309, and 920, as well as Chapter 13, IMC 2006. Reference: Section 106.3.1, IMC 2006. 2. Provide specifications and listing information for the mechanical equipment. Reference: Section 301, IMC 2006. 3. Demonstrate energy code compliance for the building envelope using calculations based on the current code. Reference: Section 101.4, International Energy Conservation Code 2006. |
| 08/22/2012 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide a site plan showing water service to the building along with the location and size of the water meter and the size, location, and type of backflow preventer. |
| 08/27/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM04819 1255 S Swan Automotive Repair 1. Must be determined and must show on Electrical if the type of repair is considered Major or Minor Repair Garage as described in the 2005 NEC,Section 511.3.A, this will determine if the repair area is unclassified or or classified. Each has different wiring methods. Review the 2005 NEC Handbook, 511.3 to determine . 2. Provide a fixture schedule showing the type of fixture, lamp and wattage used . This is required for TI's. 3. The 2005 NEC, Section 511.12 requires GFCI protection for receptacles in repair garages.Show on plan. 4. Identfy circuits B-23 and 25 on plan. Ray T Majuta Electrical Plan Review PDSD, City of Tucson 8/27/2012 Ray.Majuta@tucsonaz.gov |
| 08/29/2012 | TERRY STEVENS | ZONING | REVIEW | Denied | Zoning cannot approve the building plan until the site plan has been approved. |
| 08/29/2012 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 09/04/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/13/2012 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |