Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T12CM04818
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/01/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/08/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/08/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide structural justification for the use of a horizontal vent (i.e. a "flat vent") that does not rise vertically to a minimum of 6" above the flood rim of a fixture before it offsets horizontally. Reference: Section 905.3, UPC 2006. |
| 04/15/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/23/2013 | CPIERCE1 | OUT TO CUSTOMER | Completed |