Permit Number: T12CM04818
Parcel: 123130900

Address:
730 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T12CM04818
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2012 MARTIN BROWN FIRE REVIEW Approved
08/14/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. Please obtain separate permits for building demolition.
2. Please provide completed certification form for special inspectors.
3. Please provide structural calcualations for:
a. Wall mounted water heater, +320 lbs.
b. Accordian Door
SHEET I-221
4. Provide a large scale plan and interior elevations of the Pharmacy toilet room. It appears not to be accessible.
5. Detail 11: The urinal stall must be 3'-0" wide as per ICC A117.1, Sections 305 and 605.
6. Details 6 and P/610 conflict. Please reconcile and provide structural calculations for the support system chosen.
SHEET A-111
7. Note 22-10-4 has wrong detail reference. It should be
25/1-21.
END OF REVIEW
08/14/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed There will be demolition credits once existing buildings are demolished.
08/22/2012 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. See sheet P-610 notes. No double fittings, See sheet P-610 Detail 7. Water closet drainage shows a double fixture fitting. 2. See sheet P-610 Detail seven. Waste and vent isometric. Reference: 905.3 2006 UPC. No horizontal venting below the flood rim, unless there are structural conditions. If the floor drain is within the trap arm distance allowed, ( six feet for a three inch trap arm) then no horizontal vent is required. 3. See sheet P-610 detail two, and detail seven. Reference: 603.1 2006 UPC. Hot shall correspond to the left side of the fixture. 4. See detail six P-610. Provide a detail of how the water heater, and frame is to be mounted on the wall, and how the wall will suppot the weight. 5. Modify the fixture count schedule on P-111. Floor drain listed to have a three inch trap. Reference 702.0 2006 UPC. Fixture Unit Equivalents. 6. Clarify floor sink size. Fixture schedule does not show floor sink size. P-111 detail one, floor sink trap arm is three inch. Trap and trap arm to be the same size, Modify fixture count to reflect the correct size.
08/22/2012 RMYERS1 WATER REVIEW Approved
08/24/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust fan EF-1 so that all of the air supplied to the restrooms will be exhausted (i.e. the exhaust fan shall run whenever supply air is being introduced into the restrooms). Reference: Section 403.2.1 (4), IMC 2006.
08/29/2012 TERRY STEVENS ZONING REVIEW Approved
08/31/2012 GERRY KOZIOL WWM REVIEW Denied 1: WALGREENS - DP12-0002
2: 1 - 1/2" WATER METER PER DRAWING P-111/U2
3: NEED PCRWRD/KRISTINE GREENE REVIEW - PUBLIC SEWER NOT RELEASED AND ACCEPTED AS YET
09/04/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12cm04818
730 E Grant

Must size and indicate service entrance conductor type from 800 Amp SES to Utility Transformer, customer's contractor installs.
Provide a load for circuit 27 in panel LP-CR item 26-10-116
Sheet E-540.

Ray T Majuta
Electrical Pln Review
DSD, City of Tucson,
9/4/2012
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
11/01/2012 CINDY AGUILAR OUT TO CUSTOMER Completed