Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T12CM04818
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/10/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/14/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Please obtain separate permits for building demolition. 2. Please provide completed certification form for special inspectors. 3. Please provide structural calcualations for: a. Wall mounted water heater, +320 lbs. b. Accordian Door SHEET I-221 4. Provide a large scale plan and interior elevations of the Pharmacy toilet room. It appears not to be accessible. 5. Detail 11: The urinal stall must be 3'-0" wide as per ICC A117.1, Sections 305 and 605. 6. Details 6 and P/610 conflict. Please reconcile and provide structural calculations for the support system chosen. SHEET A-111 7. Note 22-10-4 has wrong detail reference. It should be 25/1-21. END OF REVIEW |
08/14/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | There will be demolition credits once existing buildings are demolished. |
08/22/2012 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. See sheet P-610 notes. No double fittings, See sheet P-610 Detail 7. Water closet drainage shows a double fixture fitting. 2. See sheet P-610 Detail seven. Waste and vent isometric. Reference: 905.3 2006 UPC. No horizontal venting below the flood rim, unless there are structural conditions. If the floor drain is within the trap arm distance allowed, ( six feet for a three inch trap arm) then no horizontal vent is required. 3. See sheet P-610 detail two, and detail seven. Reference: 603.1 2006 UPC. Hot shall correspond to the left side of the fixture. 4. See detail six P-610. Provide a detail of how the water heater, and frame is to be mounted on the wall, and how the wall will suppot the weight. 5. Modify the fixture count schedule on P-111. Floor drain listed to have a three inch trap. Reference 702.0 2006 UPC. Fixture Unit Equivalents. 6. Clarify floor sink size. Fixture schedule does not show floor sink size. P-111 detail one, floor sink trap arm is three inch. Trap and trap arm to be the same size, Modify fixture count to reflect the correct size. |
08/22/2012 | RMYERS1 | WATER | REVIEW | Approved | |
08/24/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fan EF-1 so that all of the air supplied to the restrooms will be exhausted (i.e. the exhaust fan shall run whenever supply air is being introduced into the restrooms). Reference: Section 403.2.1 (4), IMC 2006. |
08/29/2012 | TERRY STEVENS | ZONING | REVIEW | Approved | |
08/31/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1: WALGREENS - DP12-0002 2: 1 - 1/2" WATER METER PER DRAWING P-111/U2 3: NEED PCRWRD/KRISTINE GREENE REVIEW - PUBLIC SEWER NOT RELEASED AND ACCEPTED AS YET |
09/04/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12cm04818 730 E Grant Must size and indicate service entrance conductor type from 800 Amp SES to Utility Transformer, customer's contractor installs. Provide a load for circuit 27 in panel LP-CR item 26-10-116 Sheet E-540. Ray T Majuta Electrical Pln Review DSD, City of Tucson, 9/4/2012 Ray.Majuta@tucsonaz.gov |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/01/2012 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |