Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM04735
Parcel: 10601247B

Address:
315 E PRINCE RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM04735
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/02/2012 ROBERT SHERRY WATER REVIEW Approved
11/05/2012 GERRY KOZIOL WWM REVIEW Denied 1. AMPHITHEATER MIDDLE SCHOOL RENOVATIONS - INCLUDES NEW CLASSROOMS, ADMIN BLDG ADDT, RESTROOM ADDT, GYM REMODEL, CLASSRM T.I. AND KITCHEN REMODEL - COT PERMITS T12CM04730, T12CM04731, T12CM04732, T12CM04733, T12CM04735 AND T12CM04414
2. CONNECTING TO EXISTING ON SITE PRIVATE SEWER
3. INSTALLATION OF 3" WATER METER PER UTILITY PLAN C4.0
4. NEED TO PROVIDE INFO PRIOR TO PAYMENT FROM WATER PROVIDER FOR REMOVAL OR REPLACEMENT OF WATER METERS FOR CREDIT IF APPLICABLE

Final Status

Task End Date Reviewer's Name Type of Review Description
11/09/2012 CPIERCE1 OUT TO CUSTOMER Completed