Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM04735
Parcel: 10601247B

Address:
315 E PRINCE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM04735
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/12/2012 ROBERT SHERRY WATER REVIEW Denied Comment not resolved. The site utility drawing (C4.0) however does not include this portion of the site. Provide a site plan that indicates the source of water for buildings 300, 300-04, 300-08, 400, 500, 600, 700, and the industrial arts building, including the size of the meter and the size and type of backflow preventer.
10/12/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved; "flat venting" is allowed only when required due to significant structural problems. Note that the term "horizontal pipe" refers to a pipe which makes an angle of less than 45 degrees with the horizontal (Section 210.0, UPC 2006). Each vent pipe shall rise vertically to a minimum of 6" above the flood-level rim of the fixture it serves before offsetting horizontally. Reference: Section 905.3, UPC 2006. [Original comment: Verify that all of the new vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2006.]
10/16/2012 CPIERCE1 WWM REVIEW Needs Review