Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM04735
Parcel: 10601247B

Address:
315 E PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM04735
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2012 MARTIN BROWN FIRE REVIEW Approved
08/09/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET D1.6; DEMOLITION GENERAL NOTES: NOTE 6 REFERENCES SHEET 101-A3.1 FOR A REFLECTED CEILING PLAN. VERIFY.
2. SHEET A2.5; FLOOR PLAN GENERAL NOTES: NOTE 5 REFERENCES SHEET A10.1 FOR FRAMING DETAILS AND WALL TYPES. INCLUDE SHEET A10.2 IN THIS NOTE.
3. SHEET A2.5; FLOOR PLAN GENERAL NOTES: NOTE 7 INDICATES WINDOW INFORMATION IS ON SHEET A2.9. REVISE.
4. SHEET A2.6; ELEVATION 4: PROVIDE A DETAIL REFERENCE WHERE THE DOUBLE ANGLE LINTEL IS BEING ADDED OVER THE NEW OPENINGS IN THE EXISTING BRICK WALL.
5. SHEET A2.6; FLOOR PLANS: WHERE A NEW CONCRETE SLAB IS USED TO INFILL A DEMOLISHED PLANTER, PROVIDE A DETAIL REFERENCE FOR THE NEW SLAB AND ITS CONNECTION TO THE EXISTING CONCRETE SLAB.
6. SHEET A2.7; FLOOR PLAN: THE REFERENCE FOR THE ENLARGED RESTROOM PLAN (2/A6.2) SHOULD BE REVISED.
7. SHEET A2.9: REMOVE THE CLOUDS FROM THIS SHEET. THIS IS A FIRST CITY OF TUCSON REVIEW AND SHOULD NOT HAVE ADDENDUMS.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/22/2012 ROBERT SHERRY WATER REVIEW Denied The site utility drawing (C4.0) however does not include this portion of the site. Provide a site plan that indicates the source of water for buildings 300, 300-04, 300-08, 400, 500, 600, 700, and the industrial arts building, including the size of the meter and the size and type of backflow preventer.
08/22/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the key plan to accurately show where the proposed plumbing modifications are occurring. Reference: Section 106.3.1, IPC 2006.
2. Verify that all of the new vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2006.
08/22/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/24/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
08/27/2012 GERRY KOZIOL WWM REVIEW Denied 1. AMPHITHEATER MIDDLE SCHOOL RENOVATIONS - INCLUDES NEW CLASSROOMS, ADMIN BLDG ADDT, RESTROOM ADDT, GYM REMODEL, CLASSRM T.I. AND KITCHEN REMODEL - COT PERMITS T12CM04730, T12CM04731, T12CM04732, T12CM04733, T12CM04735 AND T12CM04414
2. CONNECTIONG TO EXISTING ON SITE PRIVATE SEWER
3. INSTALLATION OF 3" WATER METER PER UTILITY PLAN C4.0
4. NEED TO PROVIDE INFO PIROR TO PAYMENT FROM WATER PROVIDER FOR REMOVAL OR REPLACEMENT OF WATER METERS FOR CREDIT IF APPLICABLE