Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM04735
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/08/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/09/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET D1.6; DEMOLITION GENERAL NOTES: NOTE 6 REFERENCES SHEET 101-A3.1 FOR A REFLECTED CEILING PLAN. VERIFY. 2. SHEET A2.5; FLOOR PLAN GENERAL NOTES: NOTE 5 REFERENCES SHEET A10.1 FOR FRAMING DETAILS AND WALL TYPES. INCLUDE SHEET A10.2 IN THIS NOTE. 3. SHEET A2.5; FLOOR PLAN GENERAL NOTES: NOTE 7 INDICATES WINDOW INFORMATION IS ON SHEET A2.9. REVISE. 4. SHEET A2.6; ELEVATION 4: PROVIDE A DETAIL REFERENCE WHERE THE DOUBLE ANGLE LINTEL IS BEING ADDED OVER THE NEW OPENINGS IN THE EXISTING BRICK WALL. 5. SHEET A2.6; FLOOR PLANS: WHERE A NEW CONCRETE SLAB IS USED TO INFILL A DEMOLISHED PLANTER, PROVIDE A DETAIL REFERENCE FOR THE NEW SLAB AND ITS CONNECTION TO THE EXISTING CONCRETE SLAB. 6. SHEET A2.7; FLOOR PLAN: THE REFERENCE FOR THE ENLARGED RESTROOM PLAN (2/A6.2) SHOULD BE REVISED. 7. SHEET A2.9: REMOVE THE CLOUDS FROM THIS SHEET. THIS IS A FIRST CITY OF TUCSON REVIEW AND SHOULD NOT HAVE ADDENDUMS. 8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
08/22/2012 | ROBERT SHERRY | WATER | REVIEW | Denied | The site utility drawing (C4.0) however does not include this portion of the site. Provide a site plan that indicates the source of water for buildings 300, 300-04, 300-08, 400, 500, 600, 700, and the industrial arts building, including the size of the meter and the size and type of backflow preventer. |
08/22/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the key plan to accurately show where the proposed plumbing modifications are occurring. Reference: Section 106.3.1, IPC 2006. 2. Verify that all of the new vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2006. |
08/22/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
08/24/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
08/27/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1. AMPHITHEATER MIDDLE SCHOOL RENOVATIONS - INCLUDES NEW CLASSROOMS, ADMIN BLDG ADDT, RESTROOM ADDT, GYM REMODEL, CLASSRM T.I. AND KITCHEN REMODEL - COT PERMITS T12CM04730, T12CM04731, T12CM04732, T12CM04733, T12CM04735 AND T12CM04414 2. CONNECTIONG TO EXISTING ON SITE PRIVATE SEWER 3. INSTALLATION OF 3" WATER METER PER UTILITY PLAN C4.0 4. NEED TO PROVIDE INFO PIROR TO PAYMENT FROM WATER PROVIDER FOR REMOVAL OR REPLACEMENT OF WATER METERS FOR CREDIT IF APPLICABLE |