Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T12CM04731
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/02/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/02/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not addressed by the architect, second request. Provide roof drainage calculations and plans; include the effects of all side walls draining onto the roof and any contributing roof areas. All roof areas shall be drained by roof drains, scuppers, or gutters. Provide overflow protection for the roof with the parapet. Reference: Sections 1101.11.1, 1101.11.2, and 1106.0, UPC 2006. [Original comment: Provide drainage calculations and plans for the new roof sections including sizing information for the roof scupper and downspout. Provide overflow protection for the roof. Reference: Sections 1101, 1106 and 1107, IPC 2006.] |
| 11/05/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1. AMPHITHEATER MIDDLE SCHOOL RENOVATIONS - INCLUDES NEW CLASSROOMS, ADMIN BLDG ADDT, RESTROOM ADDT, GYM REMODEL, CLASSRM T.I. AND KITCHEN REMODEL - COT PERMITS T12CM04730, T12CM04731, T12CM04732, T12CM04733, T12CM04735 AND T12CM04414 2. CONNECTING TO EXISTING ON SITE PRIVATE SEWER 3. INSTALLATION OF 3" WATER METER PER UTILITY PLAN C4.0 4. NEED TO PROVIDE INFO PRIOR TO PAYMENT FROM WATER PROVIDER FOR REMOVAL OR REPLACEMENT OF WATER METERS FOR CREDIT IF APPLICABLE |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/09/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |