Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM04731
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/08/2012 | MARTIN BROWN | FIRE | REVIEW | Denied | Insufficient information. What is occupancy classification and occupant load? Please indicate exiting. Are fire sprinklers and/or fire alarms required or provided? |
| 08/08/2012 | MARTIN BROWN | FIRE | REVIEW | Denied | Insufficient information. What is occupancy classification and occupant load? Please indicate exiting. Are fire sprinklers and/or fire alarms required or provided? |
| 08/09/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET G1.2; CODE REVIEW: THE OCCUPANT LOAD ASSIGNED TO THIS PIECE OF THE PROJECT (11 OCCUPANTS) IS FOR THE NEW PORTION OF THE ADMINISTRATION AREA ONLY (1138 SF). IT IS ASSUMED THERE WAS A CERTIFICATE OF OCCUPANCY FOR THE EXISTING ADMINISTRATION SF. 2. SHEET A2.1 (FLOOR PLAN); SHEET A10.1 (WALL TYPES): THE CORRIDORS A111 AND A112 REQUIRE A ONE HOUR FIRE RATING PER THE IBC TABLE 1017.1. WALL TYPE A2 IS INDICATED ON THE PLAN. IS THE REQUIRED FIRE RATING CONSISTENT WITH THE WALL SHOWN ON SHEET A10.1? VERIFY. 3. SHEET A2.1; FLOOR PLAN: DO THE DOORS IN CORRIDORS A111 AND A112 MEET THE FIRE PROTECTION RATINGS IN THE IBC TABLE 715.4? VERIFY. 4. SHEET A2.1; FLOOR PLAN: PROVIDE THE NORTH/SOUTH GRID LINES. 5. SHEET A2.1; FLOOR PLAN: THERE IS A NORTH/SOUTH SECTION CUT 5/A5.3 ON THE FLOOR PLAN THAT CUTS THROUGH THE ENTIRE BUILDING, WHILE THE SECTION 5/A5.3 EXTENDS ONLY THROUGH THE LOBBY. CLARIFY. 6. SHEET A2.1; FLOOR PLAN: BUILDING ELEVATION 3/A5.1 (SOUTH WALL) IS SHOWN AS "SIM.". REMOVE THE SIMILAR DESIGNATION AND REVISE THE ELEVATION AS REQUIRED. 7. SHEET A2.1; FLOOR PLAN: BUILDING ELEVATION 5/A5.1 (NORTH WALL) IS SHOWN AS "SIM.". REMOVE THE SIMILAR DESIGNATION AND REVISE THE ELEVATION AS REQUIRED. 8. SHEET A2.1; FLOOR PLAN: BUILDING ELEVATION 4/A5.1 (EAST WALL) SHOWS ONLY A PORTION OF THE EAST WALL. REVISE THE ELEVATION AND MOVE THE ELEVATION INDICATOR ON THE PLAN. 9. SHEET A2.1; FLOOR PLAN: BUILDING ELEVATION 2/A5.1 (WEST WALL) SHOWS ONLY A PORTION OF THE WEST WALL. REVISE THE ELEVATION. 10. SHEET A2.9: REMOVE THE CLOUDS FROM THIS SHEET. THIS IS A FIRST CITY OF TUCSON REVIEW AND SHOULD NOT HAVE ADDENDUMS. 11. SHEET A4.1; ROOF PLAN GENERAL NOTES: NOTE 4 INDICATES ALL ROOF DETAILS ARE ON SHEET A4.1. REVISE NOTE. 12. SHEET A5.1; ELEVATIONS 2, 3, 4, AND 5: A NOTE INDICATES THE EXISTING ADMINISTRATION ELEVATION IS CONTINUED ON SHEET A5.6. REVISE THE NOTE. 13. SHEET A5.2; ELEVATIONS 1 AND 3: ARE THE NOTES DEPICTING "NEW" AND "EXISTING" CORRECT? VERIFY. 14. SHEET A7.1; ELEVATIONS 9A AND 9B: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE SECTION CUTS. 15. SHEET S1.1 (FOUNDATION PLAN); STRUCTURAL CALCULATIONS (SHEET 25): FOOTING F2 (ON GRID LINE 3) IN THE CALCULATIONS INDICATES A 1'-4" WIDE FOOTING, WHILE THE PLAN INDICATES AN F7 FOOTING (6'-0 X 10'-0 X 24" THICK). CLARIFY AND SHOW DESIGN. 16. SHEET S1.1 (FOUNDATION PLAN); STRUCTURAL CALCULATIONS (SHEET 30): THE CALCULATIONS INDICATE THE FOOTING AT THE TOWER TO BE AN F3 FOOTING (10'-6" SQUARE X 24" THICK), WHILE THE PLANS INDICATE AN F3 FOOTING (2'-0" SQUARE X 12" THICK). CLARIFY. 17. SHEET S1.1; FOUNDATION KEYNOTES: NOTES 8, 9, 10, 12, AND 15 WERE NOT FOUND ON THE PLAN. VERIFY. 18. SHEET S3.1 (ROOF FRAMING PLAN); STRUCTURAL CALCULATIONS (SHEET 12): INDICATE THE LINTEL/BEARING STUD/JAMB STUD ON THE PLAN THAT IS DESIGNED IN THE CALCULATIONS. REFERENCE A DETAIL AS REQUIRED. 19. SHEET S3.1 (ROOF FRAMING PLANS); STRUCTURAL CALCULATIONS (SHEET 14): THE CALCULATIONS INDICATE A BEAM B6 HIGH AND LOW (HSS6X6X 1/4), BUT NO BEAM IS SHOWN ON THE HIGH ROOF FRAMING PLAN. CLARIFY. 20. SHEET S3.1 (ROOF FRAMING PLANS); STRUCTURAL CALCULATIONS (SHEET 14): THE CALCULATIONS INDICATE BEAMS B7 HIGH AND LOW (HSS6X6X 1/4) ON GRID 3, BUT THERE IS ONLY ONE BEAM CALL-OUT ON THE PLANS. THE BEAM AT THE HIGH ROOF FRAMING IS A W8X21. CLARIFY. 21. SHEET S3.1 (ROOF FRAMING PLANS); STRUCTURAL CALCULATIONS (SHEET 14): THE CALCULATIONS INDICATE BEAMS B8 HIGH AND B7 LOW (HSS6X6X 1/4) ON GRID 3, BUT THERE IS ONLY ONE BEAM CALL-OUT ON THE PLANS. THE BEAM AT THE HIGH ROOF FRAMING IS A W8X21. CLARIFY. 22. SHEET S3.1; ROOF FRAMING PLAN: ON GRID 3, NOTE 16 (TWO LOCATIONS) INDICATES A STEEL STUB POST FROM THE TOP OF THE MASONRY TO THE STEEL BEAM ABOVE. PROVIDE A DETAIL. 23. SHEET S3.1; FRAMING KEYNOTES: NOTES 6, 11, AND 12 WERE NOT FOUND ON THE PLANS. VERIFY. 24. STRUCTURAL CALCULATIONS; SHEETS 25 AND 26: COLUMN C3 (HSS6X6X 1/4) IS DESIGNED AS A 24 FOOT TALL COLUMN. IS THIS JUST A STUB COLUMN? VERIFY. 25. GENERAL: SHEET A0.2 INDICATES A FLAG POLE FOUNDATION DETAIL. ARE STRUCTURAL CALCULATIONS SUBMITTED FOR THIS DESIGN? VERIFY. 26. GENERAL: ALL DEFERRED SUBMITTALS MUST BE APPROVED IN WRITING BY RON BOOSE (BUILDING OFFICIAL) BEFORE THOSE SUBMITTALS WILL BE REVIEWED. RON.BOOSE@TUCSONAZ.GOV. 27. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 08/20/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/20/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. A note on sheet P2.1.1 for the installation of the sink in the staff lounge calls for the air admittance valve to be installed "tight to underside of the counter". The air admittance valve shall be installed per the manufacturer's instructions, i.e. vertical, with sufficient clearance for removal. Reference: Section 303.2, IPC 2006. 2. Verify that the temperature mixing valve specified for the hot water distribution from WHR-A-1 is also conforms to ASSE 1070. Reference: Section 416.5, IPC 2006. 3. This building appears to be receiving all new water service from a new 3" water meter and backflow preventer and is not dependent upon any existing, unknown piping. Designing a water distribution system solely based upon water velocity can result in inadequate water pressure or flow rates at the fixtures. Provide water pressure and water pipe sizing calculations. Reference: Sections 604.1 and 604.3, IPC 2006. 4. Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2006. 5. Provide drainage calculations and plans for the new roof sections including sizing information for the roof scupper and downspout. Provide overflow protection for the roof. Reference: Sections 1101, 1106 and 1107, IPC 2006. |
| 08/20/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used. 2. Provide energy code compliance calculations for the additions to the administration building envelope (i.e. do not combine the addition to the administration building with parts of other buildings). Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4, 101.4.3, and 104.2, International Energy Conservation Code 2006. 3. Provide a smoke detector for AC-A-4; the supply air (2400 CFM) minus the outside air (275 CFM) is greater than 2,000 CFM. Reference: Section 606.1, IMC 2006. |
| 08/24/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/27/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1. AMPHITHEATER MIDDLE SCHOOL RENOVATIONS - INCLUDES NEW CLASSROOMS, ADMIN BLDG ADDT, RESTROOM ADDT, GYM REMODEL, CLASSRM T.I. AND KITCHEN REMODEL - COT PERMITS T12CM04730, T12CM04731, T12CM04732, T12CM04733, T12CM04735 AND T12CM04414 2. CONNECTIONG TO EXISTING ON SITE PRIVATE SEWER 3. INSTALLATION OF 3" WATER METER PER UTILITY PLAN C4.0 4. NEED TO PROVIDE INFO PIROR TO PAYMENT FROM WATER PROVIDER FOR REMOVAL OR REPLACEMENT OF WATER METERS FOR CREDIT IF APPLICABLE |
| 08/29/2012 | CPIERCE1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |