Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/16/2012 CAGUILA1 WWM REVIEW Needs Review
10/16/2012 CAGUILA1 PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved; provide water pressure and water pipe sizing calculations. Reference: Section 610.1, UPC 2006. [Original comment: This building appears to be receiving all new water service from a new 3" water meter and backflow preventer and is not dependent upon any existing, unknown piping. Designing a water distribution system solely based upon water velocity can result in inadequate water pressure or flow rates at the fixtures. Provide water pressure and water pipe sizing calculations. Reference: Sections 604.1 and 604.3, IPC 2006.]