Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM04730
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/16/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/16/2012 | CAGUILA1 | WWM | REVIEW | Needs Review | |
10/16/2012 | CAGUILA1 | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved; provide water pressure and water pipe sizing calculations. Reference: Section 610.1, UPC 2006. [Original comment: This building appears to be receiving all new water service from a new 3" water meter and backflow preventer and is not dependent upon any existing, unknown piping. Designing a water distribution system solely based upon water velocity can result in inadequate water pressure or flow rates at the fixtures. Provide water pressure and water pipe sizing calculations. Reference: Sections 604.1 and 604.3, IPC 2006.] |