Permit Number - T12CM04730
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 2: ROOF PLAN GENERAL NOTE 4 ON SHEET A4.2 STILL REFERENCES SHEET A4.1 (BELOW) FOR ROOF DETAILS. REVISE.
2. PREVIOUS COMMENT 8: PROVIDE A NOTE ON THE DRAWINGS (SHEETS S1.1, S1.2, AND S1.3) THAT INDICATES ALL KEYNOTES LISTED DO NOT OCCUR ON ALL SHEETS.
3. PREVIOUS COMMENT 9: NO REVISED STRUCTURAL CALCULATIONS WERE FOUND FOR STEEL BEAMS B3 AND B4 (PAGE 40 PER YOUR RESPONSE). REVISE.
4. PREVIOUS COMMENT 12: PROVIDE A NOTE ON THE DRAWINGS (SHEETS S3.1, S3.2, AND S3.3) THAT INDICATES ALL KEYNOTES LISTED DO NOT OCCUR ON ALL SHEETS.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/11/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved; provide water pressure and water pipe sizing calculations. Reference: Section 610.1, UPC 2006. [Original comment: This building appears to be receiving all new water service from a new 3" water meter and backflow preventer and is not dependent upon any existing, unknown piping. Designing a water distribution system solely based upon water velocity can result in inadequate water pressure or flow rates at the fixtures. Provide water pressure and water pipe sizing calculations. Reference: Sections 604.1 and 604.3, IPC 2006.]
10/11/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/16/2012 CPIERCE1 WWM REVIEW Needs Review