Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM04714
Parcel: 111060170

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T12CM04714
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2012 MARTIN BROWN FIRE REVIEW Approved
09/14/2012 WILDAN PLUMBING-COMMERCIAL REVIEW Approved
09/14/2012 WILDAN ELECTRICAL-COMMERCIAL REVIEW Denied Sheet E100
1. PLEASE CONFIRM THE REQUIRED SMOKE DETECTORS ARE BEING INSTALLED. IT APPEARS ONE IS MISSING FROM THE FIRST FLOOR EFFICIENCY UNIT.
2. IT IS UNCLEAR WHAT ELECTRICAL IS BEING INSTALLED IN THE UNITS. TO CONFRIM COMPLIACE PLEASE CLARLY IDENTIFY ALL EXISTING AND NEW WORK, INCLUDING THOSE ROOMS IDENTIFIED AS "HAVING MAJOR INTERIOR RENOCATIONS." THIS INCLUDED SHOWING ALL OUTLETS, LIGHTS SWITCHES ETC.
09/14/2012 GERRY KOZIOL WWM REVIEW Approved
09/14/2012 WILDAN BUILDING-COMMERCIAL REVIEW Denied Sheet AD 100/A200/A400
1. PLEASE CONFIRM THE APPLICATION OF ALL KEY NOTES,, IT APPEASE A COUPLE HAVE BEEN MISS-APPLIED AND OTHERS DO NOT APPEAR TO HAVE A DEFINITION.
Sheet A600
2. PLEASE CONFIRM THE WINDOW FORM THE SLEEPING ROOM IN APARTMENT (H) IS AN EGRESS WINDOW.
09/14/2012 GBONILL1 WATER REVIEW Needs Review
09/14/2012 WILDAN MECHANICAL-COMMERCIAL REVIEW Approved
09/14/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/14/2012 WILDAN ADA REVIEW Denied Sheet A105/A106
1. PLEASE NOTE THAT THE ACCESIBLE WATER CLOSETS WILL REQUIRE A VERTICAL GRAB BAR.
(REFERENCE ANSA A117.1 SECTION 604.5.1)
2. PLEASE CONFIRM THAT THE FLUSH HANDLES ON THE WATER CLOSETS ARE ON THE WIDE SIDE OR THE SPACE.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/19/2012 CINDY AGUILAR OUT TO CUSTOMER Completed