Permit Number: T12CM04692
Parcel: 10408001C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM04692
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. Please provide a deferred submittal approval to the building official, Mr. Ron Boose, for the truss joists.
2. Please provide a completed Certification Form for the special inspectors.
SHEET E & O
3. Detail 3: The bottom of the main accessible parking sign is to be 7'-0" a.f.g. as per COT DOT standards.
SHEET A.2
4. Detail 1: The urinal stall is to be 3'-0" wide as required by ICC A117.1, Sections 605.3 and 305.
5. Details 4, 5, 7 and 10: Please provide a horizontal bottom bar at a 4" maximum height f.f.f. as required by ICC A117.1, Section 405.9.
END OF REVIEW
08/06/2012 KEN BROUILLETTE FIRE REVIEW Approv-Cond Emergency lighting is required and may be tested for a final approval.
08/15/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide structural calculations to show that the water heater on the mezzanine is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
2. Show that the floor of the restroom slopes toward the floor drain. Reference: Section 411.2, UPC 2006.
3. Show that the construction of the site-built shower receptors complies with the requirements of Section 411.8, UPC 2006.
4. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
5. No more than one trap shall be installed on a trap arm (waste & vent diagram #6). Reference: Section 1001.1, UPC 2006.
08/15/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the new 12' ceiling fan is not, per the manufacturer's guidelines, being adversely affected by the location of the sidewall diffusers. Reference: Section 304.1, IMC 2006.
2. Verify that the amount of outside air introduced into the building is not excessively greater than the amount of air being exhausted from the building. Reference: Section 403.1, IMC 2006.
3. Revise the ventilation calculations to reflect the presence of five water closets and one urinal. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.
4. Show the outside air balancing information for the existing A/C units as well as for the new A/C units. Reference: Sections 106.3.1 and 403.3.4, IMC 2006.
5. Clarify the presence of a return grille in the massage room. Reference: Article VII, Chapter 7, Section 7-137 (3), of the Tucson Code.
08/15/2012 ROBERT SHERRY WATER REVIEW Approved
08/20/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
08/23/2012 STEVE SHIELDS ZONING REVIEW Approved
08/24/2012 GERRY KOZIOL WWM REVIEW Approved