Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM04657
Parcel: 134031450

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T12CM04657
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2012 ROBERT SHERRY WATER REVIEW Approved
08/03/2012 MARTIN BROWN FIRE REVIEW Approved
08/03/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A separate permit is required for the installation of a private sewer collection system. Reference: Title 18, R18-9-E302, 4.02 General Permit, Arizona Administrative Code.
2. Provide information to show how the proposed water heater is to be connected to the building structure. Reference: Sections 106.3.1 and 301.2, IPC 2006.
3. The architect has classified the maintenance building as S-2 (Storage). Provide the minimum plumbing facilities (e.g. drinking fountain) required by Table 2902.1, IBC 2006.
4. Clarify the piping materials to be used for the water distribution piping. Reference: Sections 604.1, 604.3, and 605.4, IPC 2006.
5. Indicate the materials to be used for the drain, waste, and vent piping. Reference: Section 702, IPC 2006.
6. The water pressure calculations are based on a total fixture demand of 9.0 fixture units but the plumbing fixture schedule indicates a total of 10.4 fixture units for the building (after subtracting the extra 15 washer wall boxes). Coordinate the two calculations. Reference: Sections 106.3.1 and 604.1, IPC 2006.
7. Verify the distance from the water meter to the furthest fixture; the civil drawings place the meter location much further than the water pressure calculations indicate.
08/03/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Provide energy code compliance calculations for the mechanical systems. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
08/03/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S2.3 (ROOF FRAMING PLAN); STRUCTURAL CALCULATIONS (SHEET 90): LINTEL BEAM LT2 INDICATES A 4X12 IN THE CALCULATIONS, BUT (2) 2X8 ON THE PLAN (REFERENCE LINTEL SCHEDULE ON SHEET S1.7). VERIFY.
2. SHEET S2.3; ROOF FRAMING PLAN: PROVIDE A REFERENCE ON THE PLAN FOR THE LINTEL SCHEDULE AND WOOD TRUSS SCHEDULE LISTED ON SHEET S1.7.
3. SHEET S3.0; DETAILS 101 AND 102: PROVIDE A NOTE OR REFERENCE FOR THE DEPTH OF THE FOOTING.
4. STRUCTURAL CALCULATIONS: PROVIDE THE POST TENSIONED SLAB DESIGN IN THE CALCULATIONS.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/09/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
08/16/2012 LOREN MAKUS ENGINEERING REVIEW Approved
08/22/2012 TERRY STEVENS ZONING REVIEW Denied Zoning cannot approve until buliding and the development plan has been approved.
08/22/2012 FRODRIG2 WWM REVIEW Denied 1. THE PLACE A PRESIDIO TRAIL - S12-017/DP12-0061 - CLUBHOUSE (18FU'S) - T12CM04333 - 13-APARTMENT BUILDINGS (3614FU'S) T12CM04334 THRU T12CM04345 & T12CM04347 - MAINTENANCE BUILDING (11FU'S) T12CM04657
2. NEED TO BUILD PUBLIC SEWER/NEED PUBLIC SEWER APPROVAL AND PUBLIC SEWER CONSTRUCTION PERMIT AND HOLD HARMLESS LETTER-NEED TO PERMIT ON-SITE PRIVATE SEWER #PT12S00910 - NEED DEQ REVIEW & APPROVAL TO CONSTRUCT ON-SITE PRIVATE SEWER - NEED COPY OF ON-SITE PRIVATE SEWER FOR BASE MAP UPDATE
3. NEED TO INDICATE SIZE OF WATER METERS ON "WATER SERVICES" TO SERVE BUILDINGS ON PUBLIC WATER PLANS - NOTE: THIRTEEN 2" WATER SERVICES" FOR 13-APARTMENT BUILDINGS AND ONE 1 1/2 "WATER SERVICE" FOR CLUBHOUSE AND ONE 1" " WATER SERVICE" FOR MAINTENANCE BUILDING FOR SEWER CONNECTION FEE CALCULATION

Final Status

Task End Date Reviewer's Name Type of Review Description
08/30/2012 CINDY AGUILAR OUT TO CUSTOMER Completed