Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2012 LOREN MAKUS ENGINEERING REVIEW Approved
07/30/2012 DAVID RIVERA ZONING REVIEW Approved
08/09/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 08-14-12
Activity: T12CM04564
Address: 3524 E. 4th St
Applicant: Gary Brummer

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide minimum 3/32" lettering per Development Standards or submit an appeal to the Building Official.
2. Clarify existing use of accessory structure. Site plan specifies carport and floor plan specifies storage.

SITE PLAN:
3. Specify the location of electrical feeders to the main service panel and to subpanel B, R106.1.1.

FLOOR PLAN:
4. Provide natural light (8% of floor area) into guest house, R303.1.

FOUNDATION PLAN:
5. Provide a foundation plan with the dimensions of footings under exterior walls.
6. Provide a note for termite treatment, R320 as amended.

STRUCTURAL / FRAMING PLAN:
7. Provide a complete braced wall panel layout showing panels at the ends (within 12.5') of all wall lines and additional panels centered at least every 25' between, Table R602.10.1.
8. Indicate all roof framing materials and spacing, R801.2.
9. Show all crickets and valleys on framing plan.
10. Provide structural drawings for the modification of the accessory structure from a carport to living space.

SECTIONS - DETAILS:
11. Provide a section detail for footings under exterior walls, R403.1.
12. Specify connection of porch roof framing to existing exterior wall.
13. Provide a cross section of the accessory structure to include minimum ceiling heights, ceiling and wall insulation, and footing depth below grade, R305.1, R319.1, R403.1.6, N1102.1.

PLUMBING PLAN:
14. Waste clean outs are required at the kitchen sink area UPC 707.4 W/ State amendment.
15. Provide consistent information regarding maximum demand of gas supply system. Schedule specifies 128,000 and layout calls for 168,000 Btu/h.
16. Provide an accurate water supply fixture unit schedule. Clarify discrepancy of the quantity of lavatories, water closets, bathtubs, showers, laundry tub, and bar sink. Clarify unit value for clothes washer.
17. Provide the maximum developed length of water line from the meter the furthest appliance served, and the diameter of the water service line and the size of the water meter, P2903.7.
18. Water meters shall be sized in accordance with the maximum design capacity per Tucson Water. A 1" meter must be supplied for demands that exceed 28 IPC fixture units.

MECHANICAL PLAN:
19. Provide a heated air source to guest house capable of maintaining a room temperature of 70 degrees at a point three feet above the floor, R303.8, 310.11.

ELECTRICAL PLAN:
20. Show subpanel B on riser diagram including feeder conductors, conduit sizes, and over-current protection (with appropriate correction factors), E3605.5.
21. Specify smoke detector locations in bedroom addition and guest house, R313.
22. Provide two or more 2O-amp circuits to supply the small appliance receptacles along kitchen counter tops. Such circuits shall be GFCI protected and shall not serve other rooms (except breakfast areas, pantries, etc.), E3801.3
23. Bathroom branch circuits shall serve no other outlets, E3603.4, E3801.6.
24. Provide an accurate electrical load calculation, E3502.2.

OUTDOOR LIGHTING CODE
25. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations.
26. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style).

INTERNATIONAL ENERGY CONSERVATION CODE:
27. Demonstrate compliance to minimum insulation values for the carport conversion to habitable living space, N1102.1.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review