Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM04479
Parcel: 11304002A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM04479
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2012 DAVID RIVERA ZONING REVIEW Denied Zoning has reviewd the building plans as part of the site review. Zoning cannot approve the building plans until the site plan is approved.
08/08/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. The City of Tucson lettering size for all construction documents is a minimum of 3/32" (actual size not font selection) for both upper and lower case. Several sheets have lettering that do not meet these minimum standards. Please change all the non compliant lettering and resubmit.
SHEET A2.2
2. Details 2 and 6: One urnial must have a 3'-0" wide stall (ICC A117.1, Sections 305 and 605.3) and the projection lip can be no higher than 17" a.f.f. (ICC A117.1, Section 605.2.
3. The structural review can not be completed as there are no foundation nor column schedules. Please reconcile and resubmit.
END OF REVIEW
08/15/2012 ROBERT SHERRY WATER REVIEW Approved
08/15/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide sufficient information to show that the installation of the new plumbing fixtures will not cause the existing water distribution system to become overloaded (i.e. are the existing water closets being replaced equipped with flush valves?). Reference: Section 101.5.1, UPC 2006.
2. Note 15 on sheet P101 calls for a new backwater valve. Verify that the building sewer downstream of the new backwater valve will be vented per Section 904.1, UPC 2006.
3. Show that the construction of the site-built shower receptor complies with the requirements of Section 411.8, UPC 2006.
4. Coordinate the architectural layout of the new shower with the plumbing design. The architectural layout is in violation of Section 411.10, UPC 2006.
5. Verify that the proposed shower control valve (Symmons model 96-500-B30-L-V) conforms to ASSE 1016. Reference: Section 418.0, UPC 2006.
08/22/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved