Permit Number: T12CM04416
Parcel: 14111003J

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM04416
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2012 MARTIN BROWN FIRE REVIEW Approv-Cond Provide Key box for fire access
07/27/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide PV panel racking foundation design and structural calculations.
2. Please provide structural calculations for:
a. The weather station pole foundation
b. Concrete pad for the converter
3. Please provide certifications for the special inspectors if required.
END OF REVIEW
08/03/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM04416
7540 S Old Vail Rd
5MV Fixed tilt Solar Project

1. Provide Specification Sheets for inverters,combiner boxes, modules, (required per our department), also this equipment must be identified and listed as per 2008 NEC,690.4(D).
2. Provide a fault current analysis beginning at utility supplied transformer on through to Inverters.
3. Provide current values at Inverter input and output terminations.

Ray Majuta
Electrical Pln Review
PDSD, City of Tucson
8/6/2012
Ray.Majuta@tucsonaz.gov
08/06/2012 ELIZABETH LEIBOLD ENGINEERING REVIEW Approv-Cond Engr will approve once Dev Pkg approved.
08/06/2012 ELIZABETH LEIBOLD ENGINEERING REVIEW Approv-Cond DEV PKG DP12-0085 APPROVED BY ENGINGEERING13AUG12.
08/14/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/14/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/15/2012 CPIERCE1 OUT TO CUSTOMER Completed