Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM04411
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/20/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/20/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The revised detail still shows the hydromechanical grease interceptor installed with a flow control device that is neither readily accessible nor visible. Install the flow control device in accordance with the code requirements and the manufacturer's instructions or select a hydromechanical grease interceptor with integral flow control. [Original comment: See sheet P4.0 detail seven, hydromechanical grease interceptor. Reference: 1014.3 2006 UPC. The flow control device for a hydromechanical grease interceptor shall be installed in a location that is readily accessible and visible. Reference: Section 1014.2.1, UPC 2006.] |
| 09/21/2012 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 09/21/2012 | CPIERCE1 | WWM | REVIEW | Needs Review |