Permit Number: T12CM04411
Parcel: 10409137B

Address:
4105 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM04411
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/20/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The revised detail still shows the hydromechanical grease interceptor installed with a flow control device that is neither readily accessible nor visible. Install the flow control device in accordance with the code requirements and the manufacturer's instructions or select a hydromechanical grease interceptor with integral flow control. [Original comment: See sheet P4.0 detail seven, hydromechanical grease interceptor. Reference: 1014.3 2006 UPC. The flow control device for a hydromechanical grease interceptor shall be installed in a location that is readily accessible and visible. Reference: Section 1014.2.1, UPC 2006.]
09/21/2012 DAVID RIVERA ZONING REVIEW Approved
09/21/2012 CPIERCE1 WWM REVIEW Needs Review