Permit Number: T12CM04380
Parcel: 10409002D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM04380
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2012 KEN BROUILLETTE FIRE REVIEW Approved
08/20/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
08/23/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied RESUBMITTAL RESPONSE COMMENTS IN UPPERCASE

GENERAL
1. OK

SHEET TS
2. Accessible note code section references are not those of the governing accessible code 2006 IBC, Chapter 11 and ICC A117.1, 2003 Edition. Please change all section references to the governing accessible listed above.
SECTION REFERENCES HAVE NO MEANING. PLEASE CHANGE ALL CODE REFERENCES TO ICC ANSI 117.1, 2003 EDITION, SECTIONS.

SHEET TS AND A2.0
3. OK

SHEET A2.0
4. Please show a finished ramp and reference all required section details and handrail details. Show the top and bottom slope ending line, all dimensions, grade elevations, slope percentage, handrails and handrail details and elevations. Please reference all these details from this ramp plan.
SECTION 1009.10 REQUIRES HANDRAILS ON BOTH SIDES OF STAIRS. PROVIDE ADDITIONAL HANDRAILS FOR THE STEPS LOCATED AT THE UPPER RIGHT AND LEFT LOCATIONS OF THE CARDIO PLATFORM.

SHEET A2.01
5. OK
6. OK
SHEET A2.2
7. OK

8. Provide a section through the lavatory counter and show all accessible requirements such as dimensions, clearances, hardware and required accessible reach distances and insulation.
DETAILS 7/A4.3 AND 8/A4.3 ARE FOR WALL MOUNTED LAVATORIES. PLEASE DETAIL A COUNTER TOP MOUNTED LAVATORY AS DESIGNED FOR THIS PROJECT.

9. OK
SHEET A3.2
10. OK

SHEET A4.0
11. Show a wall mounted handrail at detail 20.
DETAIL 15/A4.0 IS A SECTION NOT A ELEVATION OF A WALL MOUNTED HANDRAIL. PLEASE PROVIDE AN ELEVATION OF THIS HANDRAIL.

SHEET A4.3
12. Delete detail 13.
TYPO, SHOULD READ DELETE DETAIL 3.

13. OK

SHEET A5.0
14. OK
END OF REVIEW
08/24/2012 GERRY KOZIOL WWM REVIEW Denied 1. CHUZE FITNESS - DP12-0045
2. CONNECTING TO EXISTING 4" BUILDING SEWER
3. CONNECTING TO EXISTING 2" WATER LINE
4. NEED DP APPROVED / CAPACITY EVALUATION - ADDING 96FU'S
5. NEED WATER SUPPLIER UPSIZING FORM FOR SEWER CONNECTION FEE CALCULATION - DRAWING P-2 SHOWS EXISTING WATER METER NO SIZE WITH 2" PIPE TO BE FIELD VERIFIED
6. NEED TO CLARIFY SUITE NUMBER AND COMBINATION OF SUITED WITH ADDRESSING MICHELENE
08/27/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a cleanout for the clothes washer. [Original comment: Provide upper terminal cleanouts on horizontal drainage pipe over 5 feet in length. Reference: Section 707.4, UPC 2006.]
2. Comment not addressed. [Original comment: Provide details showing how the construction of the site-built shower receptor will meet the requirements of Sections 411.5 through 411.8, UPC 2006.]
3. The maximum length for a 2" trap arm is 5'-0"; the trap arms in the women's WC and the men's WC are approximately 7-feet long. [Original comment: Modify the lengths of the floor drain trap arms to as shown on the plumbing floor plan to conform to Table 10-1, UPC 2006. Reference: Section 1002.2, UPC 2006.]
08/27/2012 ROBERT SHERRY WATER REVIEW Approved
08/27/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved