Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM04380
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/24/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Please provide structural calculations for the wall mounted, 98 gallon water heater including wall analysis. SHEET TS 2. Accessible note code section references are not those of the governing accessible code 2006 IBC, Chapter 11 and ICC A117.1, 2003 Edition. Please change all section references to the governing accessible listed above. SHEET TS AND A2.0 3. Sheet TS occupant load is 332 whereas A2.0 shows an occupancy load of 298. Please reconcile. SHEET A2.0 4. Please show a finished ramp and reference all required section details and handrail details. Show the top and bottom slope ending line, all dimensions, grade elevations, slope percentage, handrails and handrail details and elevations. Please reference all these details from this ramp plan. SHEET A2.01 5. Finish drawing and indicate the ramp. 6. Indicate panic hardware for all exit doors as required by the 2006 IBC, Section 1008.1.9. SHEET A2.2 7. The accessible urinal is to have a 3'-0" stall as required by ICC A 117.1, Section 605.3 and 305 plus figure 305.7(a). 8. Provide a section through the lavatory counter and show all accessible requirements such as dimensions, clearances, hardware and required accessible reach distances and insulation. 9. As per the 2006 IBC, Section 1109.2.2 and ICC A117.1, Section 604.9, provide an ambulatory stall in the women's toilet room. SHEET A3.2 10. Detail 13, Elevation "B", please show a 3'-0" wide urinal stall. SHEET A4.0 11. Show a wall mounted handrail at detail 20. SHEET A4.3 12. Delete detail 13. 13. Detail 1, delete door signage. SHEET A5.0 14. Call out panic hardware for those doors required by the 2006 IBC, Section 1008.1.9. END OF REVIEW |
| 07/26/2012 | MARTIN BROWN | FIRE | REVIEW | Denied | Sheet TS occupant load is 332 whereas A2.0 shows an occupancy load of 298. Please reconcile. Be advised, per 2006 IFC, section 907.2.1, fire alarm required for A-3 occupancy with an occupant load of 300 or greater. |
| 07/27/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM04380 4343 N Oracle Chuze Fitness 1. Sheet E-4, provide size of circuit breaker for Panel C in Panel L2. 2. Will circuit breakers in new panels A,B and C also be fully rated for Fault Current as shown on panels as 42,000aic ? 3. Sheet E2.0, C 25,27,29 on power plan not in shcedule. 4. Sheet E2.0, L1 25,27,29 should be L2 25,27,29. 5. Please provide a detail of hoe Boost transformer to be wired in ? Ray T Majuta Electrical Review PDSD, C of Tucson 7/27/2012 Ray.Majuta@tucsonaz.gov |
| 08/01/2012 | ROBERT SHERRY | WATER | REVIEW | Denied | Revise the site drawing to show the size and route of the water supply for this activity along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. If the water meter also serves other portions of this building, indicate the total demand on the water meter Reference: Section 103.2.3, UPC 2006. |
| 08/01/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a natural gas piping design, including the piping layout on a floor plan and a natural gas schematic showing the sizes, loads and developed lengths of the piping from the meter to each load. Reference: Sections 103.2.3 and 1217.0, UPC 2006. 2. Revise the incorrect labeling of the hot water piping shown on sheet P-5. Reference: Section 103.2.3, UPC 2006. 3. The fixture schedule on sheet P-1 calls for the installation of a hot water recirculation system. Revise the plumbing floor plans, the water supply isometric, and the water heater detail to include this system if it is to be installed. Reference: Section 103.2.3, UPC 2006. 4. Note 1 of the Plumbing Energy Conservation Standards Specifications on sheet P-1 does not require the insulation of hot water run-outs of 12-feet or less. Provide justification for this specification. Reference: Section 104.2, IECC 2006. 5. Show route and termination of the T&P relief piping for WH-1. Reference: Section 608.5, UPC 2006. 6. Provide water pressure and water pipe sizing calculations. Reference: Section 610.1, UPC 2006. 7. Provide additional cleanouts in drainage pipe exceeding 100-feet in developed length. Reference: Section 707.4, UPC 2006. 8. Provide upper terminal cleanouts on horizontal drainage pipe over 5 feet in length. Reference: Section 707.4, UPC 2006. 9. Provide details showing how the construction of the site-built shower receptor will meet the requirements of Sections 411.5 through 411.8, UPC 2006. 10. Modify the lengths of the floor drain trap arms to as shown on the plumbing floor plan to conform to Table 10-1, UPC 2006. Reference: Section 1002.2, UPC 2006. |
| 08/01/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Verify that the discharge of AC-6 is located an adequate distance away from the 18-foot diameter ceiling fan per the fan manufacturer's installation documents. Reference: section 304.1, IMC 2006. 2. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson. 3. The duct insulation note # 5 of the Energy Conservation Standards Notes appears to conflict with the insulation requirements of General Note #10. Clarify the duct insulation to be installed and state the minimum required R-value of the insulation. |
| 08/08/2012 | GBONILL1 | WWM | REVIEW | Denied | 1. CHUZE FITNESS - DP12-0045 2. CONNECTING TO EXISTING 4" BUILDING SEWER 3. CONNECTING TO EXISTING 2" WATER LINE 4. NEED DP APPROVED / CAPACITY EVALUATION - ADDING 96FU'S 5. NEED WATER SUPPLIER UPSIZING FORM FOR SEWER CONNECTIONFEE CALCULATION - DRAWING P-2 SHOWS EXISTING WATER METER NO SIZE WITH 2" PIPE TO BE FIELD VERIFIED 6. NEED TO CLARIFY SUITE NUMBER AND COMBINATION OF SUITED WITH ADDRESSING MICHELENE |